[doc] Update power sync documentation
Add some notes on potential UDP packet loss during conductor/BMC power sync with IPMI, the corresponding increase in retries and how to mitigate. Change-Id: I4bc9a8f6f7f4da7f719a65f76ae97b1244701ee9
This commit is contained in:
parent
b77a76dd63
commit
28b97db915
|
@ -26,7 +26,7 @@ the services.
|
||||||
Upgrade Guide <upgrade-guide>
|
Upgrade Guide <upgrade-guide>
|
||||||
Security <security>
|
Security <security>
|
||||||
Troubleshooting FAQ <troubleshooting>
|
Troubleshooting FAQ <troubleshooting>
|
||||||
Power Sync with the Compute Service <power-sync>
|
Power Synchronization <power-sync>
|
||||||
Node Multi-Tenancy <node-multitenancy>
|
Node Multi-Tenancy <node-multitenancy>
|
||||||
Fast-Track Deployment <fast-track>
|
Fast-Track Deployment <fast-track>
|
||||||
Booting a Ramdisk or an ISO <ramdisk-boot>
|
Booting a Ramdisk or an ISO <ramdisk-boot>
|
||||||
|
|
|
@ -1,6 +1,6 @@
|
||||||
===================================
|
=====================
|
||||||
Power Sync with the Compute Service
|
Power Synchronization
|
||||||
===================================
|
=====================
|
||||||
|
|
||||||
Baremetal Power Sync
|
Baremetal Power Sync
|
||||||
====================
|
====================
|
||||||
|
@ -10,8 +10,24 @@ value of the :oslo.config:option:`conductor.force_power_state_during_sync`
|
||||||
option is set to ``true`` the power state in the database will be forced on
|
option is set to ``true`` the power state in the database will be forced on
|
||||||
the hardware and if it is set to ``false`` the hardware state will be forced
|
the hardware and if it is set to ``false`` the hardware state will be forced
|
||||||
on the database. If this periodic task is enabled, it runs at an interval
|
on the database. If this periodic task is enabled, it runs at an interval
|
||||||
defined by the :oslo.config:option:`conductor.sync_power_state_interval` config
|
defined by the :oslo.config:option:`conductor.sync_power_state_interval`
|
||||||
option for those nodes which are not in maintenance.
|
config option for those nodes which are not in maintenance. The requests sent
|
||||||
|
to Baseboard Management Controllers (BMCs) are done with a parallelism
|
||||||
|
controlled by :oslo.config:option:`conductor.sync_power_state_workers`.
|
||||||
|
The motivation to send out requests to BMCs in parallel is to handle
|
||||||
|
misbehaving BMCs which may delay or even block the synchronization otherwise.
|
||||||
|
|
||||||
|
.. note::
|
||||||
|
In deployments with many nodes and IPMI as the configured BMC protocol,
|
||||||
|
the default values of a 60 seconds power sync interval and 8 worker
|
||||||
|
threads may lead to a high rate of required retries due to client-side UDP
|
||||||
|
packet loss (visible via the corresponding warnings in the conductor
|
||||||
|
logs). While Ironic automatically retries to get the power status
|
||||||
|
for the affected nodes, the failure rate may be reduced by increasing
|
||||||
|
the power sync cycle, e.g. to 300 seconds, and/or by reducing the number
|
||||||
|
of power sync workers, e.g. to 2. Pleae keep in mind, however, that
|
||||||
|
depending on the concrete setup increasing the power sync interval may
|
||||||
|
have an impact on other components relying on up-to-date power states.
|
||||||
|
|
||||||