Add spec for IPMI support
Introduce new IPMI agent on node to poll IPMI data in periodic way Change-Id: If2d355c39120fdb9b8800901761cd9e7768fc18a
This commit is contained in:
parent
4598cdca9e
commit
641d92f28d
197
specs/juno/ipmi.rst
Normal file
197
specs/juno/ipmi.rst
Normal file
@ -0,0 +1,197 @@
|
||||
..
|
||||
This work is licensed under a Creative Commons Attribution 3.0 Unported
|
||||
License.
|
||||
|
||||
http://creativecommons.org/licenses/by/3.0/legalcode
|
||||
|
||||
============
|
||||
IPMI support
|
||||
============
|
||||
|
||||
https://blueprints.launchpad.net/ceilometer/+spec/ipmi-support
|
||||
|
||||
Add IPMI function in ceilometer, so that power/thermal data can be fetched
|
||||
through IPMI capable servers. These data can be exported to other openstack
|
||||
component for other usage, like policy control.
|
||||
|
||||
|
||||
Problem description
|
||||
===================
|
||||
|
||||
The Intelligent Platform Management Interface (IPMI) is a standardized computer
|
||||
system interface used by system administrators for out-of-band management of
|
||||
computer systems and monitoring of their operation. Enabling IPMI in ceilometer
|
||||
allows the cloud operator to monitor the power and thermal behaviors of servers
|
||||
and make reasonable operation or policy according to the real-time power/thermal
|
||||
status of data center.
|
||||
|
||||
With IPMI support,the power and thermal information of these servers can be used
|
||||
to improve overall data center efficiency and maximize overall data center
|
||||
usage. Data center managers can maximize the rack density with the confidence
|
||||
that rack power budget will not be exceeded. During a power or thermal
|
||||
emergency, we can limit server power consumption and send alert to
|
||||
administrators via the pre-defined policy.
|
||||
|
||||
Currently, Ironic project is doing work to emit notifications on the message bus
|
||||
containing IPMI sensor data, so that Ceilometer is possible to process these
|
||||
notifications for high level usage. But for nodes that are not managed by
|
||||
Ironic, IPMI data is still missing. This spec removes dependency on Ironic by
|
||||
adding IPMI support in Ceilometer.
|
||||
|
||||
Proposed change
|
||||
===============
|
||||
|
||||
Add a new IPMI agent, who get the power & thermal data via IPMI protocol in
|
||||
periodic way and publish these data via pipeline. IPMI agent lives in each IPMI
|
||||
capable node, and gets configured in deployment.
|
||||
|
||||
In this way, data can be fetched locally without credentials via network. Also
|
||||
agent polling period can be controlled by pipeline file.
|
||||
|
||||
Line up metrics with IPMI support in Ironic, so we get same IPMI data regardless
|
||||
of the underlying method (an agent-per-node directly emitting samples, or the
|
||||
ceilometer notification agent consuming notifications emitted by Ironic. If both
|
||||
available, user need deploy one only):
|
||||
|
||||
====================================== ======== ============= =========
|
||||
Name Type Unit Origin
|
||||
====================================== ======== ============= =========
|
||||
hardware.ipmi.fan g RPM p
|
||||
hardware.ipmi.temperature g C p
|
||||
hardware.ipmi.current g W p
|
||||
hardware.ipmi.voltage g V p
|
||||
====================================== ======== ============= =========
|
||||
|
||||
* g = gauge, n = notification , p = pollster
|
||||
|
||||
IPMI is generic protocol, each vendor may add specific metric for their own
|
||||
hardware. So there are probably more vendor specific metric in implementation.
|
||||
|
||||
Aim of this spec is to provide:
|
||||
1) a standard metrics that exist for most of vendor
|
||||
2) infrastructure to enable IPMI, that is, basic working unit to send IPMI
|
||||
commands.
|
||||
|
||||
It could include an simple vendor specific implementation based on 2 as example,
|
||||
so other vendor can do their own work easily.
|
||||
|
||||
|
||||
Alternatives
|
||||
------------
|
||||
|
||||
Instead of deploying IPMI agent for each node, Ceilometer itself hosts one agent
|
||||
for a bunch of nodes. It poll IPMI data from each node via network in periodic
|
||||
way. SNMP support in Ceilometer and IPMI in ironic take similar way.
|
||||
|
||||
This method avoid deploying agent in each nodes, but it introduce more work
|
||||
loads in Ceilometer itself, thus bad scalability. Furthermore, IPMI via network
|
||||
requires credential management.
|
||||
|
||||
Data model impact
|
||||
-----------------
|
||||
|
||||
None.
|
||||
|
||||
REST API impact
|
||||
---------------
|
||||
|
||||
None
|
||||
|
||||
Security impact
|
||||
---------------
|
||||
|
||||
None.
|
||||
|
||||
Pipeline impact
|
||||
---------------
|
||||
|
||||
None.
|
||||
|
||||
Other end user impact
|
||||
---------------------
|
||||
|
||||
Power/Thermal data should be exposed via the Horizon metering dashboard.
|
||||
|
||||
Performance/Scalability Impacts
|
||||
-------------------------------
|
||||
|
||||
By default, IPMI agent is not enabled until operator explicitly turn on it in
|
||||
config file for IPMI capable servers. So no performance impacts by default.
|
||||
|
||||
Other deployer impact
|
||||
---------------------
|
||||
|
||||
* IPMI config option(default off) need to be added
|
||||
|
||||
* an IPMI agent need to be added and deployed to every node, along with
|
||||
ceilometer config such as the metering secret
|
||||
|
||||
* If both Ironic and Ceilometer available for IPMI data, user need deploy one
|
||||
only
|
||||
|
||||
Developer impact
|
||||
----------------
|
||||
|
||||
None.
|
||||
|
||||
|
||||
Implementation
|
||||
==============
|
||||
|
||||
Assignee(s)
|
||||
-----------
|
||||
|
||||
|
||||
Primary assignee:
|
||||
edwin-zhai
|
||||
|
||||
Other contributors:
|
||||
lianhao-lu
|
||||
shane-wang
|
||||
|
||||
|
||||
Work Items
|
||||
----------
|
||||
|
||||
* Implement an IPMI agent for data fetching deployed in each IPMI capable node.
|
||||
|
||||
* Add unit test coverage
|
||||
|
||||
* Update related docs
|
||||
|
||||
Future lifecycle
|
||||
================
|
||||
|
||||
Once this feature enabled, need test and bug fixing in next 2 releases to avoid
|
||||
regression
|
||||
|
||||
|
||||
Dependencies
|
||||
============
|
||||
|
||||
This feature depends on IPMI capable servers
|
||||
|
||||
|
||||
Testing
|
||||
=======
|
||||
|
||||
Unit tests are sufficient since only data fetching/exporting need test.
|
||||
|
||||
Documentation Impact
|
||||
====================
|
||||
|
||||
The added metrics will need to be documented in the `measurements section`_.
|
||||
|
||||
.. _measurements section: http://docs.openstack.org/developer/ceilometer/measurements.html
|
||||
|
||||
The new configuration for deployment need to be documented.
|
||||
|
||||
IPMI agent shouldn't be deployed if a node is managed with Ironic, which need to
|
||||
be documented.
|
||||
|
||||